• 888-750-4777
  • This email address is being protected from spambots. You need JavaScript enabled to view it.
Welcome, Guest
Username: Password: Remember me
  • Page:
  • 1
  • 2

TOPIC: electrical

Re: electrical 9 years 2 months ago #61539

If anybody is still reading this post, it is basically this when it comes to AC condensers. Electricians wire to the minimum and breaker to the maximum. In other words if the largest load amps is 21.6 amps and it says maximum breaker is 40 amps. You should see a 40 amp breaker when #10 wire on it in the electrical panel. The 80% load on a wire still applies. A #12 wire would be to small of a wire but a #8 wire is not required.

Please Log in to join the conversation.

  • Page:
  • 1
  • 2
Time to create page: 0.150 seconds
© 2004-2024 Home Inspector Pro Inc. All Rights Reserved.